Process Instruments
GEORGIN has two areas of expertise, industrial instrumentation and signal interfacing for hazardous areas. With more than 30 representatives on 5 continents, representative offices in 4 countries and 3 subsidiaries abroad, Georgin is well implanted into the international market. This global reach is particularly marked in the major areas of economic growth that are Europe, Asia and the Middle-East.
Thanks to our organization, we ensure our clients and our partners a high reactivity and efficiency. Through this window on the world, Georgin promotes France’s potential and the quality of “Made in France” products.
Measurement
Control Security
Intrinsic Safety
Converters and Trip Amplifiers
Remote IO
Accessories
MEASUREMENT
Pressure transmitters, Process transmitters, Temperature transmitters,
Temperature probes, Pressure gauges, Temperature gauges.
Electronic Pressure Switch | GS/GSX series
Version: relative and absolute pressure
Range: from -1 to 400 bar (9 scales)
Technology: Thick enameled strain gauge on ceramic
Sortie: 4-20 mA – 2 wires Hart + 2 PNP, 30VCC, 200mA
Global error: +/-0,5% FS
Display: 4 digits Led, rotating (300°)
Electrical connection: M12 5 pines
Configuration: 3 sensitive touch buttons on front panel or by Hart protocol
Options:
» Current rating 1000mA
» Stainless steel version
» Diaphragm seal mounting
Transmitter GR/GA Series
Low cost model
Version: relative and absolute pressure
Range: from -1 to 250 bar
Technology: Thick enameled strain gauge on ceramic Output 4-20 mA – 2 wires
Global error: +/-0.5% FS
Options:
» Intrinsic Safety
» Oygen cleaning
Transmitter TR/TA-01 Series – Industrial mode
Version: relative and absolute pressure
Range: from -1 to 400 bar
Technology: Thick enameled strain gauge on ceramic Output 4-20 mA – 2 wires
Global error: +/-0.2% FS Setting Zero and span
Options:
» Intrinsic Safety
» Flush diaphragm
» Oygen cleaning
» Reinforced Max. P.
» Rangeability from 50 to 100% FS
TR/TA-02 Series Stainless Steel Head – Industrial model
Version: relative and absolute pressure
Range: from -1 to 400 bar
Technology: Thick enameled strain gauge on ceramic support
Output: 4-20 mA – 2 wires signal
Global error: +/-0.2% FS
Setting: Zero and span
Features:
» Stainless steel head and body (reinforced tightness)
» Screw terminal connection
» Axial or radial cable gland
Options:
» Intrinsic Safety
» Flush diaphragm
» Oygen cleaning
» Reinforced max- pressure
» Rangeability (50 to 100% FS)
Transmitter TR/TA-22 Series – Flush cell industrial type
Version: relative and absolute pressure
Range: from -1 to 50 bar
Process Connection: 1 BSPM, CLAMP or SMS
Technology: Thick enameled strain gauge on ceramic support
Output: 2 wires – 4-20 mA
Global error: +/-0.2% FS
Setting: Zero and span
Features:
» Flush ceramic cell
» No retention area and no fluid filling
» 316L stainless steel head and housing (reinforced tightness)
» Terminal connection
» Axial or radial cable gland
Options:
» Intrinsic Safety
» Flush diaphragm
» Oygen cleaning
» Reinforced P. Max.
» Rangeability of 50 to 100% FS
Transmitter TR/TA-01 Series – Industrial mode
Version: relative and absolute pressure
Range: from -1 to 400 bar
Technology: Thick enameled strain gauge on ceramic Output 4-20 mA – 2 wires
Global error: +/-0.2% FS Setting Zero and span
Options:
» Intrinsic Safety
» Flush diaphragm
» Oygen cleaning
» Reinforced Max. P.
» Rangeability from 50 to 100% FS
Transmitter SR2 Series OEM model
Version: relative pressure
Range: from -1 to 600 bar
Technology:
» Thick enameled strain gauge on ceramic support
» Piezoresistive cell
Output:
» 4-20 mA – 2 wires signal
» 0-5Vdc
» 0-10Vdc
Global error: +/- 1% FS
Options:
» Restrictor in process connection
» Special electrical connection
Relative pressure transmitter FKP series – ProcessX family
SMART Transmitter: 4-20mA + HART protocol
Span limits: -1 to 100 bar
Rangeability: 16:1
Accuracy: 0.1%
Power supply: 10.5 to 45 VDC
Process wetted parts material: 316L stainless steel
Process connection: direct
Burnout signal: according NAMUR NE43 recommendations
Long term stability: +/- 0.1% of maximum span / 10years
Options:
» Local analog or digital Indicator
» Intrinsically safe version
» Explosion proof version
» FM, CSA and IECEx certification
» Communication: Fieldbus Foundation H1, Modbus or profibus PA
» Stainless Steel electronic housing
Absolute pressure transmitter FKH series – ProcessX family
SMART Transmitter: 4-20mA + HART protocol
Span limits: 0 to 30 bar
Rangeability: 16:1
Accuracy: 0.2%
Power supply: 10.5 to 45VDC
Process wetted parts material: 316L stainless steel
Process connection: direct
Burnout: according NAMUR NE43 recommendations
Long term stability: +/- 0.1% of maximum span / 10 years
Options:
» Local analog or digital indicator
» Intrinsically safe version
» Explosion proof version
» FM, CSA and IECEx certification
» Communication: Fieldbus Foundation H1, Modbus or profibus PA
» Stainless Steel electronic housing
Differential pressure and Flow transmitter FKC series – ProcessX family
SMART Transmitter: 4-20mA + HART protocol
Span limits: 0.1 KPa to 20000KPa
Rangeability: 100:1
Accuracy: 0.065% (0.04% as an option)
Power supply: 10.5 to 45VDC
Process wetted parts material: Inox 316L, Hastelloy, Monel, Tantalum, …
Process connection: ¼”- 18NPT (oval flanges on request)
Burnout according NAMUR NE43 recommendations
Long term stability: +/- 0.1% of maximum span / 10years
Options:
» Local analog or digital Indicator
» Intrinsically safe version
» Explosion proof version
» FM, CSA and IECEX certification
» Communication : Fieldbus Foundation H1, Modbus or profibus PA
» Stainless Steel electronic housing
Relative pressure transmitter FKG series – ProcessX family
SMART Transmitter: 4- 0mA + HART protocol
Span limits: -1 to 500 bar
Rangeability: 100:1
Accuracy: 0.065% (0.04% as an option)
Power supply: 10.5 to 45VDC
Process wetted parts material: Inox 316L, Hastelloy, Monel, Tantalum, …
Process connection: ¼”-18NPT (oval flanges on request)
Burnout according NAMUR NE43 recommandations
Long term stability: +/- 0.1% of maximum span / 10years
Options:
» Local analog or digital Indicator
» Intrinsically safe version
» Explosion proof version
» FM, CSA and IECEX certification
» Communication: Fieldbus Foundation H1, Modbus or profibus PA
» Stainless Steel electronic housing
Absolute pressure transmitter FKA series – ProcessX family
SMART Transmitter: -20mA + HART protocol
Span limits: 0 to 100 bar
Rangeability : 100:1
Accuracy : 0.2% (0.1% as an option)
Power supply: 10.5 to 45VDC
Process wetted parts material: 316L st. st., Hastelloy, Monel, Tantalum, …
Process connection ¼”- 18NPT (oval flanges on request)
Burnout according NAMUR NE43 recommandations
Long term stability : +/- 0.1% of maximum span / 10years
Options:
» Local analog or digital indicator
» Intrinsically safe version
» Explosion proof version
» FM, CSA and IECEx certification
» Communication : Fieldbus Foundation H1, Modbus or profibus PA
» Stainless Steel electronic housing
Programmable converter Tia 1 series – DIN rail mounting – ProgressX Family
Input: RTD100 2 or 3 wires
Output: 4-20mA
Galvanic isolation: 1500V AC
Accuracy: <0.1% F.S. or <0.5°C Models: Standard and ATEX
Configuration: With PC (Microsoft Windows only)
EC Type examination certificate number: INERIS 13ATEX0015X
IECEx conformity certificate: INE13.0022X
ATEX/IECEx classification:
II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T135°C Da
Programmable converter Tia 2 series – DIN rail mounting – ProgressX Family
Input: Resistive sensors, TC, resistance, voltage
Output: 4-20mA
Galvanic isolation: 1500V AC
Accuracy: <-0.1% F.S. or <-0.5°C Models: Standard and ATEX
Configuration With PC (Microsoft Windows only)
EC Type examination certificate number:
INERIS 13ATEX0015X (Ex ia)
INERIS 13ATEX3006X (Ex nA)
IECEx conformity certificate:
INE13.0022X (Ex ia)
INE13.0023X (Ex nA)
ATEX/IECEx classification
II 1 G Ex ia IIC T4 Ga
II 3 G Ex nA IIC T4 Gc
II 1 D Ex ia IIIC T135°C Da
HART Programmable converter Tia 3 series – DIN rail mounting – ProgressX Family
Input: Resistive sensors, TC, resistance, voltage
Output: 4-20mA
Galvanic isolation: 1500V AC
Accuracy: <0.1% F.S. or <0.5°C Models: Standard and ATEX
Configuration With PC (Microsoft Windows only) and with HART protocol
EC Type examination certificate number:
INERIS 13ATEX0015X (Ex ia)
INERIS 13ATEX3006X (Ex nA)
IECEx conformity certificate:
INE13.0022X (Ex ia)
INE13.0023X (Ex nA)
ATEX/IECEx classification
II 1 G Ex ia IIC T4 Ga
II 3 G Ex nA IIC T4 Gc
II 1 D Ex ia IIIC T135°C Da
Programmable converter TiXo1 Series – Head mounting product – ProgressX family
Input: RTD100 2 or 3 wires
Output: 4-20mA
Accuracy: <0.1% F.S. or <0.5°C Models: Standard and ATEX
Configuration With PC (Microsoft Windows only)
EC Type examination certificate number:
INERIS 08ATEX0004X & 08ATEX3004X
ATEX classification:
Ex ia IIC T6/T5/T4
Ex iaD 20 T85/T100/T135 °C
II 3 G Ex ic IIC T6/T5/T4
HART Programmable converter TiXo3 Series – Head mounting product – ProgressX family
Input: Resistive sensors, TC, resistance, voltage
Output: 4-20mA
Galvanic isolation: 1500V AC
Accuracy: <0.1% F.S. or <0.5°C Models: Standard and ATEX
Configuration With PC (Microsoft Windows only) and with HART protocol
EC Type examination certificate number:
INERIS 08ATEX0004X & 08ATEX3002U
ATEX classification:
Ex ia IIC T6/T5/T4
Ex iaD 20 T85/T100/T135 °C
II 3 G Ex nA II T6/T5/T4
Temperature probes S series – Custom made offer or on catalog codification
Type: RTD100, RTD1000, NI100, NI1000 or thermocouple
Terminal head: DIN B, NA, KNE, BUSH, DAN, DAN V or without via cable output or special
Connection: ½ NPTM, ½ BSPP…
Options:
» With TiXo1, 2 or 3 converter
» LCD display
ATEX/IECEx classification:
EEx ia IIC T6, T5 or T4
II 2 G Ex d IIC T6
Temperature probes S series – Custom made offer or on catalog codification
Type: RTD100, RTD1000, NI100, NI1000 or thermocouple
Terminal head: DIN B, NA, KNE, BUSH, DAN, DAN V or without via cable output or special
Connection: ½ NPTM, ½ BSPP…
Options:
» With TiXo1, 2 or 3 converter
» LCD display
ATEX/IECEx classification:
EEx ia IIC T6, T5 or T4
II 2 G Ex d IIC T6
Stainless steel pressure gauge M5000 Series
Suitable for severe environments and corrosive, gaseous or liquid media which will not obstruct the pressure entry.
Version: relative pressure
Ranges: -1..1600 bar
Technology: 316L stainless steel manometric tube
304 stainless steel case: diameter 63, 100 or 150mm Safety glass
Options:
» 1 or 2 electrical switches
» ATEX Version
» Case filled with glycerine or silicon oil
» 316 stainless steel case
» Oxygen cleaning
» Bottom or lower back connection with or without flange
» Diaphragm seal or normalized flanged mounting
Industrial capsule pressure gauge M5100 Series
Suitable for low pressure, gaseous media which will not obstruct the pressure entry and severe environments.
Version: relative pressure
Ranges: -600..+600 mbar
Technology: 316L stainless steel capsule
304 stainless steel case: diameter 100 or 150 mm Safety glass
Options:
» Case filled with glycerine or silicon oil
» Oxygen cleaning
» Bottom or lower back connection with or without flange
Industrial Industrial diaphragm pressure gauge M5200 Series
Suitable for severe environments and corrosive, gaseous or liquid media which will not obstruct the pressure entry.
Version: relative pressure
Ranges: -600mbar..25 bar
Technology: 316L stainless steel diaphragm
304 stainless steel case: diameter 63, 100 or 150 mm Safety glass
Options:
» 1 or 2 electrical switches
» ATEX Version
» Case filled with glycerine or silicon oil
» 316 stainless steel case
» Oxygen cleaning
» Bottom or lower back connection with or without flange
» Normalized flange according to ISO or ANSI
“Turret” type pressure gauge M5050 Series
Suitable for severe environments and corrosive, gaseous or liquid media which will not obstruct the pressure entry.
Version: relative pressure
Ranges: -1..+1600 bar
Technology: 316L stainless steel manometric tube Black polypropylene case: diameter 4’’1/2 mm Safety glass
Options:
» Case filled with glycerine or silicon oil
» Oxygen cleaning
» Diaphragm seal or normalized flanged mounting
Differential Pressure gauge M7000 Series
Suitable for severe environments and corrosive gaseous or liquid media which will not obstruct the pressure entry.
Version: differential pressure
Ranges: 0..40 bar
Static pressure: 100 bar
Technology: 316L stainless steel double diaphragm Chambers filled with glycerine
Diaphragm sealing ring: FPM (Viton)
Bolts: stainless steel 304 stainless steel 304 case: diameter 100 or 150 mm Safety glass
Options:
» 1 or 2 electrical switches
» ATEX version
» Case filled with glycerine or silicon oil
» 316 stainless steel case
» Monel 400 (2.4360) pressure element
» Oxygen cleaning
» Bottom connection with front or back flange
Bourdon tube pressure gauge M5010 Series – Stainless steel case
Suitable for low pressure, gaseous media which will not obstruct the pressure entry and severe environments.
Version: relative pressure
Ranges: -1..1000 bar
Technology: Brass manometric tube
304 stainless steel case: diameter 63, 100 mm Window PMMA polycarbonate Case filled with glycerine
Options:
» Oxygen cleaning
» Bottom or back connection with flange or U-clamp
Bimetal Industrial Thermometer
All stainless steel bimetal industrial thermometers suitable for severe environments and corrosive media.
Ranges: -70..+500°C
Technology: Coiled bimetal
304 stainless steel case: diameter 100 or 150 mm
Connection: Bottom, back, every-angle
Process connection: Sliding or fixed Safety glass
Options:
» ATEX Version
» Filled with glycerine or silicon oil
» Special scale
» 316 stainless steel case
» oxygen cleaning
» welded or bar-stock thermowells
Differential Pressure gauge M7000 Series
Suitable for severe environments and corrosive gaseous or liquid media which will not obstruct the pressure entry.
Version: differential pressure
Ranges: 0..40 bar
Static pressure: 100 bar
Technology: 316L stainless steel double diaphragm Chambers filled with glycerine
Diaphragm sealing ring: FPM (Viton)
Bolts: stainless steel 304 stainless steel 304 case: diameter 100 or 150 mm Safety glass
Options:
» 1 or 2 electrical switches
» ATEX version
» Case filled with glycerine or silicon oil
» 316 stainless steel case
» Monel 400 (2.4360) pressure element
» Oxygen cleaning
» Bottom connection with front or back flange
CONTROL SECURITY
Georgin offers a complete range of reliable and proven
electro-mechanical solutions to control pressure and temperature:
– Pressure switches
– Temperature switches
Pressure switch with Stainless Steel housing FX Series
Version: relative, differential, absolute pressure
Ranges:
» From -1 to 1000 bar (relative pressure)
» From 0 to 100 bar (differential pressure)
Case: 316 Stainless Steel
Sensing element:
» stainless steel bellows
» NBR, FKM or EPDM diaphragm
» Stainless steel bourdon tube
Switches: 1 or 2 change over (SPDT)
Options:
» Increased safety housing (ATEX/IECEx)
» Intrinsic Safety (soon)
» SIL capability (soon)
Industrial pressure switch P Series
Version: relative, differential, absolute pressure
Ranges:
» From -1 to 1000 bar (relative pressure)
» From 0 to 90 bar (differential pressure)
Case: Zamak
Sensing element:
» Bronze or stainless steel bellows
» NBR, FKM or EPDM diaphragm
» Stainless steel bourdon tube
Switches: 1 or 2 change over (SPDT)
Options:
» Pneumatic switches
» Intrinsic Safety
» explosion-proof housing
» Increased safety housing
» GOST certificate
» VERITAS certificate
Industrial compact pressure switch F Series
Version: relative, differential, absolute pressure
Ranges:
» From -1 to 1000 bar (relative pressure)
» From 0 to 100 bar (differential pressure)
Case: Zamak or Polyester
Sensing element:
» Bronze or stainless steel bellows
» NBR, FKM or EPDM diaphragm
» Stainless steel bourdon tube
Switches : 1 or 2 change over (SPDT)
Options:
» Pneumatic switches
» Intrinsic Safety
» SIL capability
» explosion-proof housing
» Increased safety housing
» GOST certificate
Pressure switch – Low pressure AIRGAS Series –
For ventilators security and burners control
Version: relative and differential pressure
Ranges:
» From -500 to 1100 mbar (relative pressure)
» From 0 to 1100 mbar (differential pressure)
Case: Coated steel
Sensing element:
» NBR, FKM or EPDM diaphragm, aluminium alloy flange
Switch: 1 or 2 change over (SPDT)
Options:
» Intrinsic Safety
Industrial pressure switch – Very low pressure – (D)MLFK Series
For ventilations, air or gas fouling, unit heater flow, …
Version: relative and differential pressure
Ranges:
» From -1.5 to 1 mbar (relative pressure)
» From 0 to 2.5 mbar (differential pressure)
Case: Coated steel
Sensing element:
» NBR or FKM diaphragm, stainless steel flange
Switch: 1 change over (SPDT)
Options:
» Intrinsic Safety
Pneumatic pressure switch C Series – For cabinet mounting
These pressure switches have been specially designed for dedicated applications such as gas mixers and essentially mounted in cabinets.
Version: relative pressure
Ranges: from -1 to 20 bar
Tightness: IP20
Sensing element:
» NBR, FKM or EPDM diaphragm
Function: 1 pneumatic cell NO or NF
Options:
» Constructional safety for ATEX areas by cabinet integration
Compact pressure switch G Series
Version: relative pressure
Range: From -1 to 400 bar
Case: composite material
Sensing element:
» Bronze or stainless steel bellows
» Stainless steel Bourdon tube
Switch: 1 or 2 change over (SPDT)
Options:
» Intrinsic Safety
Temperature switch with Stainless Steel housing FX Series
Version: direct bulb or capillary
Ranges: -90..+380°C
Case: 316 Stainless Steel
Sensing element: IP66/67
Sensing element: Stainless steel bulb and capillary
Switch: 1 or 2 change over(SPDT)
Options:
» Stainless steel armour or PVC coated capillary
» Increased safety housing (ATEX/IECEx)
» Intrinsic Safety (soon)
» SIL capability (soon)
Industrial temperature switch P Series
Version: direct bulb or capillary
Ranges: -50..+600°C
Case: Zamak
Sensing element: Stainless steel or copper bulb and capillary
Switch: 1 or 2 change over(SPDT)
Options:
» Stainless steel armour or PVC coated capillary
» Pneumatic switch
Options:
» Intrinsic Safety
» Explosion-proof housing
» Increased safety housing
» GOST certificate
» VERITAS certificate
Compact temperature switch G Series
Version: direct bulb or capillary
Ranges: -20..+250°C
Case: Composite material
Sensing element: Stainless steel or copper bulb and capillary
Switch: 1 or 2 change over(SPDT)
Options:
» Intrinsic Safety
» SIL capability
Industrial compact temperature switch F Series
Version: direct bulb or capillary
Ranges: -90..+380°C
Case: Zamak or polyester
Sensing element: Stainless steel or copper bulb and capillary
Switch: 1 or 2 change over(SPDT)
Options:
» Stainless steel armour or PVC coated capillary
» Pneumatic switch
Options:
» Intrinsic Safety
» Explosion-proof housing
» Increased safety housing
» SIL capability
» GOST certificate
Low cost temperature switch U Series
Version: With capillary
Ranges: -20..+210°C
Case: Composite material
Sensing element: Copper bulb and capillary
Switch: 1 switch
Options:
» SIL capability
» APSAD
INTRINSIC SAFETY
Intrinsic Safety is one of the protection methods used for instruments installed in hazardous areas. Georgin offers a large range of Intrinsically safe devices:
Zener barriers, Switching amplifier, Isolator, Converters, Power supply, Field mounted indicators, Bargraphs, Set point stations, Pilot lamps
Programmable converter, trip amplifier UI – ProgressX family
Universal programmable converter with threshold relay function. Configurable via PC using the ProgressX Manager software and micro USB standard or by the BlueSet removable display.
Input: Universal Voltage
Current Thermocouples
RTD100, 2/3/4 wires
2/3 wires sensors Potentiometers
Output:
1 x 4-20mA or 0/10 V
1 SPDT or 2 configurable SIL relays
Power supplies:
Vcc and Vac universal power supply, 24/48 Vdc group power supply with back connector.
LEDs Intelligent signaling flashing for defaults.
Configuration: By progressX Manager for programming the type of input, relays state in case of fault, hysteresis and alarm temporisation, 4/20mA output.
Possibility for line measurement and outputs simulation. By the BlueSet removable display, it allows the adjustment of input type, unit, scale,
represented value, square root extraction, SIL function, status of fault relays, mode, value, hysteresis and delay of alarm relays, output simulation, current output navigation via 1 control joystick. The BlueSet console allows to save a typical configuration to copy it in other appliances of the same reference.
Installation: Safe area
Options:
» removable display BlueSet
» power supply with back connector
» Standard micro USB cable
» downloadable Progress X manager software
ATEX classification :
CE 0081 II (1) G/D
[Ex ia]IIC et [Ex ia] IIIC
[Ex ia]IIB et [Ex ia] IIIB
Zener barrier BZG series
Zener barriers are designed to limit energy which may appear in hazardous area.
Mounting: simple on DIN rail
Models: simple or double
Version: 1 or 2 channels on 13mm tightness
Installation in safe area or in Zone 2 in a IP54 housing (nA type of protection)
Front panel with removable label holder
Options:
» Current flow signaling LED on the front
» Barrier / DIN-rail isolator
» Ex d housing – RTPE9-DIN or other Ex d / Ex e enclosure
EC Type examination certificate number : INERIS 11 ATEX 0024 X
IECEx conformity certificate : INE 11.0009X
ATEX/IECEx classification :
II (1) GD [Ex ia Ga] IIC or [Ex ia Ga] IIB or [Ex iaD Da] IIIC
II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
II 3 (1) G Ex nA [ia Ga] IIB T4 Gc
Zener barrier BZC series
Zener barriers are designed to limit energy which may appear in hazardous area.
Mounting:on copper terminal or on DIN rail with a mounting kit
Models:simple or double Installation in safe area or in hazardous area in an explosion proof enclosure
Options:
» DIN rail mounting kit
» Ex d housing – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number :
LCIE 01 ATEX 6070 X
ATEX classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Programmable converter – Trip amplifier BPX Series – ProgressX family (UI)
BPX are designed to convert RTD100, thermocouples, potentiometer, mA, mV and other standardized current signals coming from the hazardous area to the safe area.
Input: Universal
Output: up to 2 4/20mA outputs and 4programmable thresholds depending on model
Supply: VAC ou VDC
Red LEDfor alarm state, and green LED for presence of voltage
Installation: Safe area progressX Manager for programming the type of input,
relays state in case of fault, hysteresis and alarm temporisation, 4/20mA output
Possibility for line measurement and outputs simulation
Options:
» Hart signal transparency with the barrier
» Screw terminals
» RS232 programming cable and USB / RS232 converter
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE03 ATEX 6469X
ATEX classification :
II (1) GD [Ex ia] IIC ou [Ex ia] IIB ou [Ex iaD]
Intrinsically safe relay RDN Series – (DI)
This device is designed to relay digital signals coming from a switch or a proximity sensor installed in hazardous area to the safe area.
Input: Switch or proximity sensor
Output: Switch (5A – 250V) or transistor (5kHz)
Supply: 24-48 VDC, 110 VAC or 230 VAC
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Red LEDfor relay state, and
green LED for presence of voltage
Installation : Safe area
Options:
» Alarm (loop integrity with proximity sensor)
» Screw terminals
» Icc current limited to 20mA or 5mA according to codification
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
4-20mA transmitter power supply BXNT(I) – BXLT(I) – BXMT(I) Series – (AI)
This device is designed to interface 4/20mA signals coming from the hazardous to the safe area.
Input: 4/20mA 2 wires active or passive
Output: 4/20mA 2 wires active or passive
Supply: 24-48 VDC, 110 VAC or 230 VAC
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Setting: Adjustment potentiometer for the source and the curve on the front
green LED for presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with the barrier (BXNTI – BXLTI – BXMTI)
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Galvanic isolated converter BXNT(I) Series – (AI)
This device is designed to interface and convert signals coming from the hazardous to the safe area.
Input: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Output: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC
Model: 1 channel
Setting: Adjustment potentiometer for the source and the curve on the front green LED for presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with the barrier (BXNTI)
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Galvanic isolated converter BXNR – BXNC – BXNP – (AI)
This device is designed to interface and convert RTD100, linear resistor, thermocouples or potentiometer signals coming from the hazardous to the safe area.
Input:
» BXNR: RTD100 with fixed scale to be defined according codification
» BXNRV: Linear resistor
» BXNC: Thermocouple with fixed scale and type to be defined according codification
» BXNP: Potentiometer from 0- 1kOhm to 0–50kOhm
Output: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC
Model: 1 channel
Setting: Adjustment potentiometer for the source and the curve on the front green LEDfor presence of voltage
Installation : Safe area
Options:
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Intrinsically safe power supply BXNE Series – (DO)
This device is designed to supply instruments in hazardous area. Control by 24V remote control or by switch in safe area.
Input: without (direct supply), 24VDC remote control or switch
Output: different intrinsically safe parameters according to model
Supply: 24-48 VDC or 110- 230 VAC
Model: 1 or 2 channels green LEDfor presence of voltage and red LED for remote control activaton
Installation : Safe area
Options:
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Converter for actuator BXNA(I) Series – (AO)
This device is designed to interface and convert signals coming from the safe to the hazardous area.
Input:Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Output: Current (4/20mA)
Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC
Model: 1 channel
Setting:Adjustment potentiometer for the source and the curve on the front green LEDfor presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with the barrier (BXNAI)
» Screw terminals
» ACCDIVBX power supply cables
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
4-20mA loop galvanic isolator BXNI*A – BXNI*T Series – (AO – AI)
This device is designed to isolate 4/20mA signals between the safe and the hazardous areas.
Input:Current (4/20mA)
Output: Current (4/20mA)
Supply: No power supply required
Model: 1, 2 or 4 channels
Setting:Adjustment potentiometer for the source on the front
Installation : Safe area
Options:
» Screw terminals
» Ex d enclosure – RTPE9-DIN or other Ex d enclosure
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
I.S. Field mounted indicator GeXi04 – GeXi24 – Local mounting
4/20 mA loop powered intrinsically safe field mounted indicator. Located in hazardous area, this indicator displays the current flowing in a 4/20 mA loop in engineering units.
Input: 4/20mA
Supply: Loop powered only 1.2V drop (2 wires)
Setting:Front panel push buttons
Installation : Zone 0, 1 or 2 ; 20, 21 or 22 (as an option)
Models:
» GeXi04 (4 digits 20 000 points high 34mm)
» GeXi24 (5 digits 200 000 points high 29mm)
Options:
» 2 alarms
» Backlight
» External keypad
» Stainless legend plate
» Dust area version
EC Type examination certificate number: ITS11ATEX27253
ATEX classification :
II (1) G Ex ia IIC T5 Ga
II (1) D Ex ia IIIC T80°C Da IP66*
I.S. pilot lamp VSI05 series – Panel mounting Ø22.5mm
Installation: Zone 0, 1 or 2
Colour: Red, Green, Yellow, Blue and White
EC Type examination certificate number:
ITS13ATEX27822X
ATEX classification :
II 1G Ex ia IIC T4 Ga
BEKA’s range Georgin, Beka’s distributor
Distribution areas:
» France
» Marocco
» Tunisia
» Algeria
View the full Beka’s range:
» Indicating temperature transmitters (BA474D, BA478C, …)
» Serial text [Data] displays (BA384D, BA488C,…)
» Fieldbus indicators & displays (BA414DF, BA444DF, BA418CF, BA448CF, BA484DF, BA488CF, …)
» Rate totalisers (BA334D, 338C, 344D, 354E, 358E, …)
» Rate totalisers (BA334D, 338C, 344D, 354E, 358E, …)
» Set point stations (BA405C, …)
» Flow batch controllers (BA454D, BA458C, …)
» Counter, timer, tachometer & clock (BA364D, BA368C, …)
» IS battery powered clock (BA369)
» Exd sounders & beacons (BExS, BExBG, BExCS)
» Exi sounder & beacon (BR385, BA386)
I.S. relay BED Series – (DI) – Backplane mounting
This device is designed to relay digital signals coming from a switch or a proximity sensor installed in hazardous area to the safe area.
Input: Switch or proximity sensor
Output: Switch (5A – 250V) or transistor (5kHz)
Supply: 24-48 VDC, 110 VAC or 230 VAC
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Red LEDfor relay state, and green LED for presence of voltage
Installation : Safe area
Options:
» Alarm (loop integrity with proximity sensor)
» Screw terminals
» Icc current limited to 20mA or 5mA according to codification
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Galvanic isolated converter BET(I) Series – (AI) – Backplane Mounting
This device is designed to interface and convert signals coming from the hazardous to the safe area.
Input: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Output: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Supply: 24 VDC
Model: 1 channel
Setting: Adjustment potentiometer for the source and the curve on the front
green LED for presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with the barrier (BETI)
» Screw terminals
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaaD]
Intrinsically safe power supply BEE Series – (DO) – Backplane Mounting
This device is designed to supply instruments in hazardous area. Control by 24V remote control or by switch in safe area.
Input:without (direct supply), 24VDC remote control or switch
Output: different intrinsically safe parameters according to model
Supply: 24-48 VDC, 110VAC or 230 VAC
Model: 1 or 2 channels green LEDfor presence of voltage and red LED for remote control activaton
Installation : Safe area
Options:
» Screw terminals
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Converter for actuator BEA(I) Series – (AO) – Backplane Mounting
This device is designed to interface and convert signals coming from the safe to the hazardous area.
Input:Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Output: Current (4/20mA)
Supply: 24 VDC
Model: 1 channel
Setting:Adjustment potentiometer for the source and the curve on the front
green LED for presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with
the barrier (BEAI)
» Screw terminals
EC Type examination
certificate number:
LCIE 02 ATEX 6104X
IECEx conformity
certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia]
IIB or [Ex iaD]
4-20mA loop galvanic isolator BEI*A Series – (AO) – Backplane Mounting
This device is designed to isolate 4/20mA signals between the safe and the hazardous areas.
Input: Current (4/20mA)
Output: Current (4/20mA)
Supply: No power supply required
Model: 1, 2 or 4 channels
Setting: Adjustment potentiometer for the source on the front
Installation : Safe area
Options:
» Screw terminals
EC Type examination certificate number:
LCIE 02 ATEX 6104X
IECEx conformity certificate :
LCI 09.0013X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Backplane for plug-in modules P Series
Backplane allowing a very compact and flexible mounting of our «plug-in» modules BED, BEA, BET, BER/C/P, BEI series into any system cabinet. The easy engineering and small density reduce costs and installation volumes.
Capacity: 8 or 16 modules
Options:
» Earth rail
» connection by one multiways connector
» Alarm
» Tag plate
Programmable converter – Trip amplifier
LPX Series – ProgressX family (UI) – Rack 19″ mounting
This card is designed to convert RTD100, thermocouples, potentiometer, mA, mV and other standardized current signals coming from the hazardous area to the safe area.
Input: Universal
Output: up to 2 4/20mA outputs and 4 programmable threshold depending on model
Supply: VAC ou VDC
Red LEDfor alarm state, and green LED for presence of voltage
Installation: Safe area progressX Manager for programming the type of input, relays state in case of fault, hysteresis and alarm temporisation, 4/20mA output
Possibility for line measurement and outputs simulation
Options:
» Hart signal transparency with the barrier
» RS232 programming cable and USB / RS232 converter
EC Type examination certificate number:
LCIE03 ATEX 6469X
ATEX classification :
II (1) GD [Ex ia] IIC ou [Ex ia] IIB ou [Ex iaD]
Intrinsically safe relay CRN Series – (DI) – Rack 19″ mounting
This card is designed to relay digital signals coming from a switch or a proximity sensor installed in hazardous area to the safe area.
Input: Switch or proximity sensor
Output: 1 or 2 switches according models
Supply: 24-48 VDC, 110 VAC or 230 VAC
Model: 2, 3 or 6 channels
Red LED for relay state, and
green LED for presence of voltage
Installation : Safe area
Options:
» With or without keying pin
EC Type examination
certificate number:
LCIE 03 ATEX 6408X
ATEX classification :
II (1) GD [Ex ia] IIC or [Ex ia] IIB or [Ex iaD]
Galvanic isolated converter LXR – LXC – LXP Series – (AI) – Rack 19″ mounting
This card is designed to interface and convert RTD100, linear resistor, thermocouples or potentiometer signals coming from the hazardous to the safe area.
Input:
» LXR: RTD100 with fixed scale to be defined according codification
» LXC: Thermocouple with fixed scale and type to be defined according codification
» LXP: Potentiometer from 0- 1kOhm to 0–50kOhm
Output: Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC
Model: 2 channels
Setting: Adjustment potentiometer for the source and the curve green LEDfor presence of voltage
Installation : Safe area
Options:
» With or without keying pin
EC Type examination certificate number:
LCIE 02 ATEX 6431X
ATEX/IECEx classification :
II (1) GD [Ex ia] IIC ou [Ex ia] IIB ou [Ex iaD]
Converter for actuator LW0 – LW0I Series – (AO) – Rack 19″ mounting
This card is designed to interface and convert signals coming from the safe to the hazardous area.
Input:Current (4/20mA – 0/20mA…), Voltage (0/5V – 0/10V…) or other on request
Output: Current (4/20mA)
Supply: 24 VDC, 48 VDC, 110 VAC or 230 VAC
Model: 2 channels
Setting:Adjustment potentiometer for the source and the curve green LED for presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with
the barrier (LWOI)
» With or withoutkeying pin
EC Type examination
certificate number:
LCIE03 ATEX 6469X
ATEX classification :
II (1) GD [Ex ia] IIC ou [Ex ia]
IIB ou [Ex iaD]
19″ rack PAE B10 / 30 / 40 Series – European cards system
Plug-in terminals Rack for use with European Georgin format cards (100 x 220 mm), wired to the card by a DIN 41612C type connector.
Capacity: 14 cards
Supply: Trough screw terminal common to the 14 cards
19″ rack PAE 1153 / 1154 Series – European cards system
Rack wired with flat cables and screw terminals for use with european format cards (100 x 220 mm) with DIN 41612C type connector.
Models:
» PAE 1153 : fixed frame
» PAE 1154 : pivot mounted frame
Capacity: 14 cards
Supply: Trough screw terminal common to the 14 cards
CONVERTERS AND TRIP AMPLIFIERS
Georgin offers a wide range of conventional devices for signal conversion and display solutions.
Converters, Trip amplifiers, 4/20mA process or temperature indicator
Programmable converter, trip amplifier UI – ProgressX family
Universal programmable converter with threshold relay function. Configurable via PC using the ProgressX Manager software and micro USB standard or by the BlueSet removable display.
Input: Universal Voltage, Current Thermocouples RTD100, 2/3/4 wires 2/3 wires sensors Potentiometers
Output: 1 x 4-20mA or 0/10 V | 1 SPDT or 2 configurable SIL relays
Power supplies: Vcc and Vac universal power supply, 24/48 Vdc group power supply with back connector. LEDs Intelligent signaling flashing for defaults.
Configuration: By progressX Manager for programming the type of input, relays state in case of fault, hysteresis and alarm temporisation, 4/20mA output. Possibility for line measurement and outputs simulation.
By the BlueSet removable display, it allows the adjustment of input type, unit, scale, represented value, square root extraction, SIL function,
status of fault relays, mode, value, hysteresis and delay of alarm relays, output simulation, current output navigation via 1 control joystick. The BlueSet console allows to save a typical configuration to copy it in other appliances of the same reference.
Installation: Safe area
Options:
» removable display BlueSet
» power supply with back connector
» Standard micro USB cable
» downloadable ProgressXmanager software
ATEX classification:
CE 0081 II (1) G/D
[Ex ia]IIC et [Ex ia] IIIC
[Ex ia]IIB et [Ex ia] IIIB
Signal conditioners SG Series – galvanic isolation module 6mm thickness
Mounting: rail DIN ou rail alimenté
Inputs: current, voltage, Pt100, TC sensors…
Outputs: 4/20mA, current, voltage
Power supply: 16.8 to 31.2 Vdc
Consumption: 0.8 to1.2W
Accuracy: 0.1% of full scale
Configuration: by DIP switches or USB using GEORGINSet* software
Isulation: >KV between input, output and power supply
Models:
GT 45000 – Temperature transmitter
GS 75000 – Shunt resistance isolation amplifier / voltages in mV
GN 25000 – Isolation amplifier
GN 21000 – Signal separator / repeater
GH 11000 (1 channel) and
GH 11020 (2 channels) – Isolator powered by the loop
GC 52500 – HART transmitter power supply
GB 64000 – Bipolar isolation amplifier
Programmable converter – Trip amplifier BPX Series – ProgressX family (UI)
BPX are designed to convert RTD100, thermocouples, potentiometer, mA, mV and other standardized current signals.
Input: Universal
Output: up to 2 4/20mA outputs and 4programmable thresholds depending on model
Supply: VAC ou VDC
Red LEDfor alarm state, and
green LED for presence of voltage
progressX Manager for programming the type of input, relays state in case of fault, hysteresis and alarm temporisation, 4/20mA output
Possibility for line measurement and outputs simulation
Options:
» Hart signal transparency with the barrier
» Screw terminals
» RS232 programming cable and USB / RS232 converter
» ACCDIVBX power supply cables
4-20mA transmitters supply BVNT(I) – BVLT(I) – BVMT(I) Series – (AI)
This device is designed to interface 4/20mA signals.
Input: 4/20mA 2 wires active or passive
Output: 4/20mA 2 wires active or passive
Supply: 24-48 VDC, 110-230 VAC
Model: 1 or 2 channels and signal duplicator (1 input – 2 outputs)
Setting: Adjustment potentiometer for the source and the curve on the front
green LEDfor presence of voltage
Installation : Safe area
Options:
» Hart signal transparency with the barrier (BVNTI – BVLTI – BVMTI)
» Screw terminals
» ACCDIVBX power supply cables
Universal indicator GSI 48 Series – Universal input – Panel mounting
Process indicator for analogue signals. Displaying a process, temperature, load cell or potentiometer signal in engineering units.
Mounting: 48x96mn panel
Input: Process, RTD100, Thermocouple
Display: 4.5 digits
Supply: 10-70 Vdc and 21-53 Vac or 85-260 Vac and 100- 300 Vdc
Options:
» Alarms (2x, 4x)
» 4…20mA output
» Workshop configuration with test report
Universal indicator GSI 40 series – Universal input – Panel mounting
Process indicator for analogue signals. Displaying a process, temperature, resistance, potentiometer signal in engineering units.
Mounting: 48x96mn panel
Input: Process, RTD100,
Thermocouple
Display: 4 digits
Supply: Universal 12 to 265
VDC and 20 to 265 VAC
Options:
» Alarms (2x, 4x)
REMOTE I/O
Georgin analyses and offers Remote I/O solutions with Profibus or Modbus
communication protocol.
With a proven know-how, Geogin proposes remote I/O solutions for all type of applications in hazardous area.
Characteristics:
» Interfacing of all type of signals (DI, DO, AI, AO)
» Installation in stainless steel or GRP (glass reinforced plastic)
» Main communication protocols: Profibus, Modbus RTU or TCP IP, Ethernet and Protocole de communication Profibus, Modbus RTU ou TCP IP, Ethernet et transmission by optical fibre as an option
» Supply and communication redundancy as an option
ACCESSORIES
To complete the supply of measurement, control and safety devices, Georgin offers classic associable accessories:
Welded or standardized flange diaphragm seals, Welded or barstock thermowells, Pressure gauge valves or manifolds, Accessories for pulsating or vibrating process, Temperature limiting devices
Monobloc diaphragm seal to screw S131 series – Low cost model
Function:Process connection to screw
Working pressure: 0 to 160 bar
Food and pharmaceutical industries diaphragm seal S300 Series
Function:CLAMP, SMS or DIN11851 connection
Working pressure: -1 to 40 bar
Flush diaphragm seal S770 – S630 – S640 – S650 series
Function:Rotating flange connection
Working pressure: -1 to 600 bar
Dismountable diaphragm seal to screw
S771 – S631 – S641 – S651 Series
Function:Process connection to screw
Working pressure: -1 to 600 bar
Diaphragm seals to weld S772 – S632 – S642 – S652 series
Flange to weld on process
Working pressure: -1 to 600 bar
Compact standardized flange diaphragm seals
S680 – S660 Series
Flange according to ISO or ANSI B16-5
Working pressure: PN10 to PN100 – 150# to 600#
Diaphragm seals to weld S772 – S632 – S642 – S652 series
Flange to weld on process
Working pressure: -1 to 600 bar
Compact standardized flange diaphragm seals
S680 – S660 Series
Flange according to ISO or ANSI B16-5
Working pressure: PN10 to PN100 – 150# to 600#
Standardized flange diaphragm seals
S773 – S633 – S643 – S653 Series
Flange according to ISO or ANSI B16-5
Working pressure:PN10 to PN100 – 150# to 600#
Process transmitter seals FKSEP Series – ProcessX Family
The FKSep family proposes a wide modularity of industrial seals specifically designed to fit the constraints inherent to ProcessX family transmitters. Rigid direct mounting or with capillary separator.
Construction:
» Flush mounting from DN400 to DN 100
» Extention seals (50 to 200 mm)
» Flange type adapters, with fitting to seal or screw
» Seals with sanitary DIN, SMS or Clamp connections
» Other specific seals on demand
Options:
» Diaphragm or gasket surface made with special materials
Pressure gauge valves A3200 Series
brass, steel, 316 Ti st. st.
Process connection: 1/2” GM ou 1/2” NPTM
Siphon A3000 / A3010 Series
Function:To prevent over-heating
2 types: Trompet form or monobloc
Material: steel, stainless steel
Process connection: 1/2″ BSP M or 1/2″; NPT M
Dampener
A3100 Series
Function:Protection against pulsations
Material: brass or stainless steel
Connection: 1/2″ BSP M or 1/2″ NPT M
Overpressure protector
A3400 Series
Function:Protection against peak pressure and pulsations
Material: stainless steel
Process connection: 1/2″ BSP M or 1/2″ NPT M
Thermowell
Function: Temperature switch bulb mechanical protection
Construction: Welded or barstock
Process wetted parts material: stainless steel, tantalum, Hastelloy, PTFE, Monel…
Option:
» Thermoconductive paste tube
Welded connection A3500 / A3600 / A3700 Series A3500
Function: Connection for welding instrument
Material: steel, brass or stainless steel
A3600
Function: Food connection for instrument
Material: stainless steel
Process connection: clamp, SMS or DIN
A3700
Function: Turning connection allowing the positioning of a measuring instrument
Material: stainless steel
2, 3 or 5 valves Manifolds
A33**-2/-3/-5 Serie
Function: isolation, equalisation, calibration and venting
Material: 316L st. st. + PTFE packing
Process connection: 1/2″NTPF, flange connection, other on request